Every conductor has some resistance, so a little voltage is always lost pushing current along a cable — that loss is the voltage drop. For a single-phase run the drop is Vdrop = 2 × ρ × L × I / A, where the factor 2 accounts for the current travelling out to the load and back along the return conductor; a three-phase run uses √3 instead of 2. Here ρ is the resistivity of the metal (copper ≈ 0.0175 Ω·mm²/m, aluminium ≈ 0.0282 Ω·mm²/m), L is the one-way length in metres, I the load current in amps and A the conductor cross-section in mm². This calculator also reports the resulting percentage drop, the voltage actually delivered at the load and the power wasted as heat in the cable (Ploss = Vdrop × I).

As a worked example, take 20 A flowing 50 m one-way through a 10 mm² copper cable on a 230 V single-phase supply: Vdrop = 2 × 0.0175 × 50 × 20 / 10 = 3.5 V, about 1.5%, so the load sees roughly 226.5 V and the cable wastes 3.5 × 20 = 70 W. Switch the conductor to aluminium and the same run drops about 5.6 V, because aluminium’s resistivity is around 60% higher. You can either type a custom cross-section or pick a standard AWG gauge from the advanced list, which overrides the area field with the gauge’s real mm² value.

Voltage drop matters because motors, lights and electronics misbehave when they are starved of voltage — dim lamps, sluggish motors and nuisance tripping all trace back to oversized drops on long runs. Electricians size cables so total drop stays within about 3% for branch circuits and 5% end-to-end; the result here flags whether your run meets the limit you set, and the fix for a failing run is a larger conductor, a shorter route or, occasionally, a higher supply voltage.

Tambayoyi da ake yi da yawa

Yadda ake ƙididdigewa nauyi na wutar lantarki?

Ga mataki guda, Vdrop = 2 × ρ × L × I / A. Ma'aunin 2 yana da alhakin tafiyar yanzu zuwa waje da baya; mataki uku yana amfani da √3 a matsayin 2.

Menene voltage drop ne yarda?

A al'ada na al'ada na al'ada ne don a kiyaye duk raguwa a karkashin 3% ga sassan da 5% a cikin gaba ɗaya. Mafi girma masu jagoranci (mafi girma yanki) rage raguwa.

Shin, kunã cẽwa, "Allah ne."

Yes. Aluminium has about 60% higher resistivity than copper, so an aluminium run of the same size drops proportionally more voltage.

Why does the formula use twice the length?

Current has to flow out to the load and back, so a single-phase circuit sees the drop of both conductors — hence the factor of 2 × length. Three-phase circuits use √3 (about 1.732) instead, reflecting the geometry of balanced three-phase power.

Yadda za a rage wani voltage da yawa?

Use a larger conductor (doubling the cross-section roughly halves the drop), shorten the run, split the load across parallel cables, or raise the supply voltage. Bigger copper is the usual fix because drop is inversely proportional to area.

Menene ƙarfin da aka rasa a cikin kebul?

The power wasted is the drop times the current, Ploss = Vdrop × I. A 3.5 V drop at 20 A wastes 70 W as heat in the wire — energy you pay for but never use, which is why long high-current runs justify thicker, lower-loss cable.

Shin zan iya amfani da ma'aunin AWG a matsayin wani yanki na mm²?

Ya. Zaɓi wani ma'aunin a cikin jerin AWG na ci gaba kuma ya canza filin yankin da wannan ma'aunin na cross-section a cikin mm² (misali 10 AWG ≈ 5.26 mm²), don haka zaka iya aiki a cikin tsarin ma'aunin da masu shigarwa na North American ke amfani da su.

❤️ Love Calculator.Free? Share

𝕏  X Facebook Reddit
API — amfani da wannan calculator daga code

Ka kira wannan kwalban kamar wata maɓallin ƙarshe JSON mai kyauta - babu maɓalli da ake buƙata. Ka aika kimar fannin ƙasa kamar paramita na tambaya ko JSON. Anything you omit uses the same default this page is pre-filled with; an unknown parameter is a 400, never a silent zero. Read the full API docs →

Endpoint

GET https://calculator.free/api/v1/voltage-drop/

curl

curl "https://calculator.free/api/v1/voltage-drop/?material=copper&length=50&current=20&area=10&source=230"

JavaScript fetch()

const r = await fetch(
  "https://calculator.free/api/v1/voltage-drop/?" + new URLSearchParams({
    "material": "copper",
    "length": "50",
    "current": "20",
    "area": "10",
    "source": "230"
  }));
const data = await r.json();
console.log(data.results);

Results are estimates for general guidance only, not financial, medical or tax advice.